Bộ đổi nguồn Din-Rail 220VAC sang 12VDC 40W MCTT-MDR-40-12


Features:
|
SPECIFICATIONS |
|
|
OUTPUT |
|
|
Model |
MCTT-MDR-40-12 |
|
DC Voltage |
12V |
|
Rated Current |
3.3A |
|
Current Range |
0-3.3A |
|
Rated Power |
40W |
|
Ripple & Noise |
120mVp-p |
|
Voltage Adj. Range |
-8%,+10% |
|
Voltage Tolerance |
±1% |
|
Setup, Rise Time |
500ms,30ms/230VAC500ms,30ms/115VAC at full load |
|
Hold Up Time |
50ms/230VAC20ms/115VAC at full load |
|
INPUT |
|
|
Voltage Range |
88~264VAC47~63Hz; 124~370VDC |
|
AC Current |
1.1A/115V0.7A/ 230V |
|
Efficiency |
86% |
|
Inrush Current |
Cold start 30A/115V60A/230V |
|
Leakage Current |
<1mA/240VAC |
|
PROTECTION |
|
|
Over Load |
105%~160% |
|
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
|
|
Over Voltage |
115%~135% |
|
Protection type: Shut down o/p voltage, re-power on to recover |
|
|
ENVIRONMENT |
|
|
Working Temp., Humidity |
-20℃~+60℃; 20%~90%RH |
|
Storage Temp., Humidity |
-40℃~+85℃; 10%~95%RH |
|
Temp. Coefficient |
±0.03%/℃(0~50℃) |
|
Vibration |
10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
|
SAFETY |
|
|
Withstand Voltage |
I/P-O/P: 3KVAC |
|
Isolation Resistance |
I/P-O/P: 100M Ohms / 500VDC |
|
STANDARD |
|
|
Safety Standard |
Design refer to UL60950-1,TUV EN60950-1,EN50178 |
|
EMC Standard |
Design refer to EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2,EN61204-3 |
|
OTHERS |
|
|
Dimension |
40*90*100mm(W*H*L) |
|
Weight |
0.33Kg |
|
Packing |
50pcs/carton |
|
NOTE |
|
|
1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25℃ of ambient temperature. 2.Ripple & noise are measured at 20MHz of bandwidth by using a 12”twisted pair-wire terminated with a 0.1μ & 47μparallel capacitor. 3.Tolerance: includes set up tolerance, line regulation and load regulation. 4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. |
|